Implementation
Type |
Output voltage |
Current |
ZI-1 | 5V DC | 10A |
ZI-2 | 12V DC | 4A |
ZI-3 | 18V DC | 3A |
ZI-4 | 24V DC | 2A |
ZI-5 | 15V DC | 3,3A |
ZI-6 | 48V DC | 1A |
Attention!
* Below 160V input power supply voltage will continue to stabilize the output voltage, but the maximum output current will decrease concurrent with a decline in input voltage.
* Due to the high frequency converter, some very sensitive radio or microprocessor can operate correctly. It is recommended that you install the filter OP-230 (see item 18) between the power supply and receiver.
* By increasing the load above Imax will stabilize power supply current, but output voltage will decrease. If a outputvoltage falls to about 40% of the power supply is switched off and will be 1.5 ÷ 2sec. sample. Similarly happens when you connect the receiver, which receives a large current boot (ie the cold light bulb). If you're experiencing is not too large, the power supply after a few attempts (eg, the gradual warming-up, the light bulb filaments) runs. If the load is too large to sample the power supply will disconnect the load moment.
Technical data
input voltage | 85÷264V AC |
output power | 50W |
current limitation | l max = 110% of output current |
minimum load | 0% |
keying frequency | 70kHz |
working temperature | -10÷40°C |
connection | screw terminals 2,5mm² |
dimensions | 6 modules (105mm) |
weight | 190g |
fixing | on rail 35mm |
Electric suppliers
- Product Code: ZI-1-6