PEL - differential pressure transmitters are made for clean / isolation room applications. The zero point of the transmitter remains exact by means of the automatic zeroing, eliminating regularly possible zero point drifting.
Technical data
Product number: 1131110 / 1131111
Range: selectable at commissioning: 0...100, 0...200, 0...500, 0...1000 Pa, -50...50, -100...100, -250...250 or -500...500 Pa
Mounting: with screws, external lugs
Housing: IP 54, cable gland downwards
Supply: 24 Vac/dc
Ambient temperature: 0...45 °C
Output: 0...10 V < 2 mA or 4...20 mA < 900 Ω