Purpose
To control the "star"-"delta" contactor connection system.
Functioning
The PCG-417 relay is equipped with a special system of two electromagnetic relays which removes the risk of activating two connectors simultaneously, with each relay controlling a given connector. Once the system is switched from "star" to "delta", one relay disconnects the "star" connector (a forced interval takes place). The other then activates the “delta” connector.
After the power supply is turned on, the contact 7-9 is closed and remains in this position for the preset start-up time t1. After the lapse of t1, contact 7-9 opens and both contacts remain open for the time t2. After the lapse of t2, the contact 10-12 is closed and remains in this position until the power voltage is disconnected.
Technical data
| supply | 230V AC / 24V AC/DC |
| current load | 2×(<8A) |
| contact | 2×1C/O |
| start-up time "star" | 1÷1000sec |
| switching time "delta" | 75msec / 150msec |
| power supply indicator | LED green |
| action indicator | LED red |
| power consumption | 0,8W |
| working temperature | 25÷50°C |
| connection | screw terminals 2,5mm² |
| dimensions | 1 module (18mm) |
| fixing | on rail TH-35 |
Star-delta switch time controller
- Product Code: PCG-417