Purpose
Three phase monitor serves to protect the three-phase electric motors supplied from three-phase mains, against phase collapse in at least one phase or against phase-to-phase voltage asymmetry or against damage of contacts threatening to damage the motor.
Technical data
supply | 3×400/230V+N |
contact | 1C/O |
current load | <10A |
signalling of supply | 2 × LED |
activation voltage asymmetry | 40÷55V~ |
activation voltage | 175÷190V~ |
histeresis | 5V~ |
switch-OFF delay | 3÷5sec |
power consumption | 1,6W |
working temperature | -25÷50°C |
connection | screw terminals 2,5mm² |
dimensions | 3 modules (52,5mm) |
fixing | on rail TH-35 |
Three-phase monitors with checking state of contactor contacts
- Product Code: CZF-332