Purpose
Three phase monitors serve to protect the three-phase electric motors supplied from three-phase mains, against phase collapse in at least one phase or against phase-to-phase voltage asymmetry, threatening to damage the motor.

Technical data

 

supply 3×400/230V+N
contact 1C/O
current load <10A
signalling of supply 3×LED in each phase circuit
activation voltage asymmetry 40÷80V~
histeresis 5V~
switching-off delay 4sec
power consumption 1,6W
working temperature -25÷50°C
connection screw terminals 2,5mm²
dimensions 2 modules (35mm)
fixing on rail TH-35

Three-phase asymmetry and sequence monitors

  • Product Code: CKF-BT
  • 0.00€

  • Ex Tax: 0.00€