Purpose
Three phase monitors serve to protect the three-phase electric motors supplied from three-phase mains, against phase collapse in at least one phase or against phase-to-phase voltage asymmetry, threatening to damage the motor.
Technical data
supply | 3×400V |
current load | <10A |
activation voltage asymmetry | 20÷50V~ |
activation voltage | <320V~ |
histeresis | 5V~ |
switching-OFF delay | 4sec |
signalling of supply | 4 × LED |
power consumption | 1,6W |
working temperature | -25÷40°C |
connection | screw terminals 2,5mm² |
dimensions | 3 modules (52,5mm) |
fixing | on rail TH-35 |
Three-phase asymmetry and sequence monitors
- Product Code: CKF-337