TEPK LL temperature transmitter is designed for measuring heating and cooling water temperatures in HVAC automation systems. The sensor is mounted on the pipe by using the heat resistance cable tie. Pt1000 sensor element resistance information is converted to 4…20 mA signal. Tthe ML-SER commissioning tool can be used to make one point field calibration and to change the temperature output to controller output.
Technical data
Product number: 1177240
Range: 4 selectable ranges
Housing: IP54 (cable gland downwards)
Cable entry: M16
Accuracy: ±0.5 °C (at 0 °C)
Time constant: about 5 s
Materials: PC plastic, zinc cast
Cable: 2 m, LIYY 2 x 0,14
Sensor: Pt1000 EN 60751/B
Ambient temperature: -30…60 °C
Output: 4…20 mA