• Mid energy counters
Technical features
Power supply
  • Power supplied from the voltage lines
  • Voltage range: 180 ... 290 V L-N
  • Max consumption (for each phase): 3,5 VA - 1 W
  • Frequency: 50/60 Hz
Voltage
  • Range:
    3x230/400V ... 3x240/415V 50/60Hz 4 wires
Current
  • Starting current I st: 20 mA
  • Minimum current I min: 250 mA
  • Transitional current I tr: 500 mA
  • Reference current I ref (Ib): 5 A
  • Maximum current I max: 80 A

RS485 Modbus communication
  • Port: RS485
  • Protocol: Modbus RTU/ASCII
  • Communication speed: 300 ... 57600 bps

M-Bus communication
  • Port: wired (EN 1434-3)
  • Protocol: M-Bus
  • Communication speed: 300 ... 38400 bps
  • Unit load: 1
Ethernet communication
  • Port: 10/100 Base T
  • Protocol: HTTP, NTP, DHCP, Modbus TCP
  • Communication speed: 10/100 Mbps
  • Data recording

Accuracy
  • Active energy class 1 according to IEC/EN 62053-21
  • Reactive energy class 2 according to IEC/EN 62053-23

S0 output
  • Passive optoisolated
  • Maximum values: 27 V DC - 27 mA
  • Pulse length: 50 ±2ms ON time

Tariff input (not available with Ethernet model)
  • Active optoisolated
  • Maximum voltage: 276 V AC-DC

Metrological LED
  • Meter constant: 1000 pulse/kWh

Environmental conditions
  • Operating temperature: -25°C ... +55°C
  • Storage temperature: -25°C ... +75°C
  • Humidity: 80% max without condensation
  • Protection degree: IP51 frontal part - IP20 terminals

Mid energy counters

  • Brand: Algodue
  • Product Code: UEM80-4D
  • 0.00€

  • Ex Tax: 0.00€